| GROUP PDF | GEN ET POWER H SERIE 10-650kVA (0,9 P.F.*) with IGBT RECTIFIER | |||||||
| UPS | BATTERY OPTIONS | TIME | ||||||
| Model | Power | Battery Qty | Battery | Battery Cabinet | Battery Cable Breaker | Time (Minutes) | ||
| GEN ET-310SH | 10kVA | 60 | 12V 4,5AH | BCS6405 | Included | 6 / 14 | ||
| 60 | 12V 7AH | BCS6607 | Included | 15 / 45 | ||||
| 60 | 12V 9AH | BCS6607 | Included | 23 / 54 | ||||
| 60 | 12V 12AH | BC40 | OPT | 30 / 68 | ||||
| 120 | 12V 7AH | BC40 | OPT | 47 / 104 | ||||
| 120 | 12V 9AH | BC40 | OPT | 56 / 118 | ||||
| Model | Power | Battery Qty | Battery | Battery Cabinet | Battery Cable Breaker | Time (Minutes) | ||
| GEN ET-315SH | 15kVA | 60 | 12V 4,5AH | BCS6405 | Included | 4 / 10 | ||
| 60 | 12V 7AH | BCS6607 | Included | 6 / 26 | ||||
| 60 | 12V 9AH | BCS6607 | Included | 14 / 32 | ||||
| 60 | 12V 12AH | BC40 | OPT | 16 / 46 | ||||
| 120 | 12V 7AH | BC40 | OPT | 29 / 63 | ||||
| 120 | 12V 9AH | BC40 | OPT | 34 / 71 | ||||
| 60 | 12V 24AH | BC01MP-2K | OPT | 54 / 118 | ||||
| Model | Power | Battery Qty | Battery | Battery Cabinet | Battery Cable Breaker | Time (Minutes) | ||
| GEN ET-320SH | 20kVA | 60 | 12V 4,5AH | BCS6405 | Included | 3 / 7 | ||
| 60 | 12V 7AH | BCS6607 | Included | 4 / 15 | ||||
| 60 | 12V 9AH | BCS6607 | Included | 9 / 23 | ||||
| 120 | 12V 7AH | BC40 | OPT | 18 / 47 | ||||
| 120 | 12V 9AH | BC40 | OPT | 23 / 57 | ||||
| 60 | 12V 24AH | BC01MP-2K | OPT | 38 / 82 | ||||
| 120 | 12V 18AH | BC01MP-2K | OPT | 62 / 155 | ||||
| 60 | 12V 40AH | BC01MP-2K | OPT | 68 / 165 | ||||
| Model | Power | Battery Qty | Battery | Battery Cabinet | Battery Cable Breaker | Time (Minutes) | ||
| GEN ET-330H | 30kVA | 60 | 12V 9AH | Included | Included | 5 / 14 | ||
| 120 | 12V 7AH | AKÜ 10T | OPT | 6 / 29 | ||||
| 120 | 12V 9AH | AKÜ 10T | OPT | 14 / 34 | ||||
| 60 | 12V 24AH | BC01MP-2K | OPT | 23 / 57 | ||||
| 120 | 12V 18AH | BC01MP-2K | OPT | 39 / 96 | ||||
| 60 | 12V 40AH | BC01MP-2K | OPT | 43 / 98 | ||||
| Model | Power | Battery Qty | Battery | Battery Cabinet | Battery Cable Breaker | Time (Minutes) | ||
| GEN ET-340H | 40kVA | 60 | 12V 9AH | Included | Included | 4 / 9 | ||
| 120 | 12V 7AH | Included | OPT | 6 / 15 | ||||
| 120 | 12V 9AH | Included | OPT | 9 / 23 | ||||
| 60 | 12V 24AH | BC01MP-2K | OPT | 16 / 39 | ||||
| 120 | 12V 18AH | BC01MP-2K | OPT | 27 / 62 | ||||
| 60 | 12V 40AH | BC01MP-2K | OPT | 30 / 68 | ||||
| 120 | 12V 24AH | 2 x BC01MP-2K | OPT | 39 / 93 | ||||
| Model | Power | Battery Qty | Battery | Battery Cabinet | Battery Cable Breaker | Time (Minutes) | ||
| GEN ET-360H | 60kVA | 60 | 12V 18AH | Included | Included | 4,5 / 15 | ||
| 60 | 12V 20AH | Included | Included | 6 / 18 | ||||
| 60 | 12V 24AH | BC01MP-2K | OPT | 9 / 23 | ||||
| 120 | 12V 18AH | BC01MP-2K | OPT | 14 / 39 | ||||
| 60 | 12V 40AH | BC01MP-2K | OPT | 14 / 43 | ||||
| 120 | 12V 24AH | 2 x BC01MP-2K | OPT | 23 / 54 | ||||
| 60 | 12V 70AH | 2 x BC01MP-2K | OPT | 34 / 84 | ||||
| 60 | 12V 80AH | 2 x BC01MP-2K | OPT | 39 / 88 | ||||
| Model | Power | Battery Qty | Battery | Battery Cabinet | Battery Cable Breaker | Time (Minutes) | ||
| GEN ET-380H | 80kVA | 60 | 12V 20AH | Included | Included | 4 / 11 | ||
| 120 | 12V 18AH | BC01MP-2K | OPT | 9 / 27 | ||||
| 60 | 12V 40AH | BC01MP-2K | OPT | 9 / 30 | ||||
| 120 | 12V 24AH | 2 x BC01MP-2K | OPT | 16 / 39 | ||||
| 60 | 12V 70AH | 2 x BC01MP-2K | OPT | 24 / 58 | ||||
| 60 | 12V 80AH | 2 x BC01MP-2K | OPT | 27 / 61 | ||||
| 60 | 12V 105AH | 2 x BC01MP-2K | OPT | 42 / 91 | ||||
| Model | Power | Battery Qty | Battery | Battery Cabinet | Battery Cable Breaker | Time (Minutes) | ||
| GEN ET-3100H | 100kVA | 120 | 12V 18AH | BC01MP-2K | OPT | 5 / 19 | ||
| 60 | 12V 40AH | BC01MP-2K | OPT | 5 / 20 | ||||
| 120 | 12V 24AH | 2 x BC01MP-2K | OPT | 10 / 29 | ||||
| 60 | 12V 70AH | 2 x BC01MP-2K | OPT | 14 / 44 | ||||
| 60 | 12V 80AH | 2 x BC01MP-2K | OPT | 20 / 47 | ||||
| 60 | 12V 105AH | 2 x BC01MP-2K | OPT | 32 / 69 | ||||
| * Battery duration are calculated as %100 and %50 loads. | ||||||||
| * Battery duration are calculated under 0,7 Pf. | ||||||||
| * Generg will supply min. 10 years spare parts for the products. | ||||||||
| * Warranty is 2 years for manufacturer defects. | ||||||||
| Power Factor Options and Suffixes at the end of the model name | ||||||||
| H - PF Cos Ø 0,9 | ||||||||
| HA - PF Cos Ø 0,8 | ||||||||
| HB - Pf Cos Ø 1 | ||||||||