GROUP PDF |
GEN ET POWER H SERIE 10-650kVA (0,9 P.F.*)
with IGBT RECTIFIER |
UPS |
BATTERY OPTIONS |
TIME |
Model |
Power |
Battery
Qty |
Battery |
Battery
Cabinet |
Battery
Cable Breaker |
Time (Minutes) |
|
GEN ET-3120H |
120kVA |
120 |
12V 18AH |
BC01MP-2K |
OPT |
4 / 12 |
|
60 |
12V 40AH |
BC01MP-2K |
OPT |
4 / 14 |
|
120 |
12V
24AH |
2 x BC01MP-2K |
OPT |
9 / 23 |
|
60 |
12V
70AH |
2 x BC01MP-2K |
OPT |
10 / 34 |
|
60 |
12V
80AH |
2 x BC01MP-2K |
OPT |
16 / 39 |
|
60 |
12V 105AH |
2 x BC01MP-2K |
OPT |
27 / 58 |
|
120 |
12V 70AH |
4 x BC01MP-2K |
OPT |
34 / 84 |
|
Model |
Power |
Battery
Qty |
Battery |
Battery
Cabinet |
Battery
Cable Breaker |
Time (Minutes) |
|
GEN ET-3160H |
160kVA |
60 |
12V 40AH |
BC01MP-2K |
OPT |
3 / 9 |
|
120 |
12V
24AH |
2 x BC01MP-2K |
OPT |
5 / 16 |
|
60 |
12V
70AH |
2 x BC01MP-2K |
OPT |
5 / 24 |
|
60 |
12V
80AH |
2 x BC01MP-2K |
OPT |
9 / 26 |
|
60 |
12V 105AH |
2 x BC01MP-2K |
OPT |
19 / 42 |
|
120 |
12V
70AH |
4 x BC01MP-2K |
OPT |
24 / 58 |
|
120 |
12V
80AH |
4 x BC01MP-2K |
OPT |
26 / 61 |
|
Model |
Power |
Battery Qty |
Battery |
Battery Cabinet |
Battery Cable
Breaker |
Time (Minutes) |
|
GEN ET-3200H |
200kVA |
60 |
12V 70AH |
2 x BC01MP-2K |
OPT |
4 / 14 |
|
60 |
12V
80AH |
2 x BC01MP-2K |
OPT |
5 / 21 |
|
60 |
12V 105AH |
2 x BC01MP-2K |
OPT |
13 / 32 |
|
120 |
12V
70AH |
4 x BC01MP-2K |
OPT |
14 / 44 |
|
120 |
12V
80AH |
4 x BC01MP-2K |
OPT |
20 / 47 |
|
120 |
12V 105AH |
4 x BC01MP-2K |
OPT |
32 / 74 |
|
Model |
Power |
Battery Qty |
Battery |
Battery Cabinet |
Battery Cable
Breaker |
Time (Minutes) |
|
GEN ET-3250H |
250kVA |
60 |
12V 80AH |
2 x BC01MP-2K |
OPT |
4 / 15 |
|
60 |
12V 105AH |
2 x BC01MP-2K |
OPT |
6 / 25 |
|
120 |
12V
70AH |
4 x BC01MP-2K |
OPT |
9 / 32 |
|
120 |
12V
80AH |
4 x BC01MP-2K |
OPT |
15 / 35 |
|
120 |
12V 105AH |
4 x BC01MP-2K |
OPT |
25 / 56 |
|
180 |
12V 105AH |
6 x BC01MP-2K |
OPT |
40 / 88 |
|
Model |
Power |
Battery Qty |
Battery |
Battery Cabinet |
Battery Cable
Breaker |
Time (Minutes) |
|
GEN ET-3300H |
300kVA |
60 |
12V 105AH |
2 x BC01MP-2K |
OPT |
4 / 20 |
|
120 |
12V
70AH |
4 x BC01MP-2K |
OPT |
5 / 25 |
|
120 |
12V
80AH |
4 x BC01MP-2K |
OPT |
10 / 29 |
|
120 |
12V 105AH |
4 x BC01MP-2K |
OPT |
20 / 45 |
|
180 |
12V 105AH |
6 x BC01MP-2K |
OPT |
32 / 70 |
|
Model |
Power |
Battery Qty |
Battery |
Battery Cabinet |
Battery Cable
Breaker |
Time (Minutes) |
|
GEN ET-3400H |
400kVA |
60 |
12V 105AH |
2 x BC01MP-2K |
OPT |
3 / 13 |
|
120 |
12V
70AH |
4 x BC01MP-2K |
OPT |
4 / 14 |
|
120 |
12V
80AH |
4 x BC01MP-2K |
OPT |
5 / 21 |
|
120 |
12V
105AH |
4 x BC01MP-2K |
OPT |
14 / 32 |
|
180 |
12V
105AH |
6 x BC01MP-2K |
OPT |
24 / 51 |
|
Model |
Power |
Battery Qty |
Battery |
Battery Cabinet |
Battery Cable
Breaker |
Time (Minutes) |
|
GEN ET-3550 |
550kVA |
120 |
12V 80AH |
4 x BC01MP-2K |
OPT |
3 / 13 |
|
120 |
12V
100AH |
4 x BC01MP-2K |
OPT |
4 / 18 |
|
120 |
12V
105AH |
4 x BC01MP-2K |
OPT |
5 / 20 |
|
180 |
12V
80AH |
6 x BC01MP-2K |
OPT |
7 / 23 |
|
180 |
12V
100AH |
6 x BC01MP-2K |
OPT |
9 / 30 |
|
180 |
12V
105AH |
6 x BC01MP-2K |
OPT |
17 / 40 |
|
Model |
Power |
Battery Qty |
Battery |
Battery Cabinet |
Battery Cable
Breaker |
Time (Minutes) |
|
GEN ET-3650 |
650kVA |
120 |
12V 100AH |
4 x BC01MP-2K |
OPT |
3 / 13 |
|
120 |
12V
105AH |
4 x BC01MP-2K |
OPT |
4 / 18 |
|
180 |
12V
100AH |
6 x BC01MP-2K |
OPT |
6 / 25 |
|
180 |
12V
105AH |
6 x BC01MP-2K |
OPT |
10 / 30 |
|
|
|
|
|
|
|
|
|
|
|
* Battery duration are
calculated as %100 and %50 loads. |
|
|
|
* Battery duration are
calculated under 0,7 Pf. |
|
|
|
* Generg will supply
min. 10 years spare parts for the products. |
|
|
|
* Warranty is 2 years
for manufacturer defects. |
|
|
|
Power Factor Options and
Suffixes at the end of the model name |
|
|
|
H - PF Cos Ø 0,9 |
|
|
|
HA - PF Cos Ø 0,8 |
|
|
|
HB - Pf Cos Ø 1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|