| GROUP PDF | ET POWER HA SERIES 10-201kVA (0,8.P.F) with IGBT BATTERY CHARGE | ||||||||
| UPS | BATTERY OPTIONS | TIME | |||||||
| Model | Power | Battery Qty | Battery | Battery Cabinet | Battery Cable Breaker | Time (Minutes) | |||
| GEN ET-330SHA | 30kVA | 60 | 12V 9AH | BCS6607 | Included | 5 / 14 | |||
| 120 | 12V 7AH | BC40 | OPT | 6 / 29 | |||||
| 120 | 12V 9AH | BC40 | OPT | 14 / 34 | |||||
| 60 | 12V 24AH | BC01MP-2K | OPT | 23 / 57 | |||||
| 120 | 12V 18AH | BC01MP-2K | OPT | 39 / 96 | |||||
| 60 | 12V 40AH | BC01MP-2K | OPT | 43 / 98 | |||||
| Model | Power | Battery Qty | Battery | Battery Cabinet | Battery Cable Breaker | Time (Minutes) | |||
| GEN ET-340HA | 40kVA | 60 | 12V 9AH | Included | Included | 4 / 9 | |||
| 120 | 12V 7AH | BATTERY 10T | OPT | 6 / 15 | |||||
| 120 | 12V 9AH | BATTERY 10T | OPT | 9 / 23 | |||||
| 60 | 12V 24AH | BC01MP-2K | OPT | 16 / 39 | |||||
| 120 | 12V 18AH | BC01MP-2K | OPT | 27 / 62 | |||||
| 60 | 12V 40AH | BC01MP-2K | OPT | 30 / 68 | |||||
| 120 | 12V 24AH | 2 x BC01MP-2K | OPT | 39 / 93 | |||||
| Model | Power | Battery Qty | Battery | Battery Cabinet | Battery Cable Breaker | Time (Minutes) | |||
| GEN ET-360A | 60kVA | 60 | 12V 18AH | Included | Included | 4,5 / 15 | |||
| 60 | 12V 20AH | Included | Included | 6 / 18 | |||||
| 60 | 12V 24AH | BC01MP-2K | OPT | 9 / 23 | |||||
| 120 | 12V 18AH | BC01MP-2K | OPT | 14 / 39 | |||||
| 60 | 12V 40AH | BC01MP-2K | OPT | 14 / 43 | |||||
| 120 | 12V 24AH | 2 x BC01MP-2K | OPT | 23 / 54 | |||||
| 60 | 12V 70AH | 2 x BC01MP-2K | OPT | 34 / 84 | |||||
| 60 | 12V 80AH | 2 x BC01MP-2K | OPT | 39 / 88 | |||||
| Model | Power | Battery Qty | Battery | Battery Cabinet | Battery Cable Breaker | Time (Minutes) | |||
| GEN ET-380HA | 80kVA | 60 | 12V 20AH | Included | Included | 4 / 11 | |||
| 120 | 12V 18AH | BC01MP-2K | OPT | 9 / 27 | |||||
| 60 | 12V 40AH | BC01MP-2K | OPT | 9 / 30 | |||||
| 120 | 12V 24AH | 2 x BC01MP-2K | OPT | 16 / 39 | |||||
| 60 | 12V 70AH | 2 x BC01MP-2K | OPT | 24 / 58 | |||||
| 60 | 12V 80AH | 2 x BC01MP-2K | OPT | 27 / 61 | |||||
| 60 | 12V 105AH | 2 x BC01MP-2K | OPT | 42 / 91 | |||||
| Model | Power | Battery Qty | Battery | Battery Cabinet | Battery Cable Breaker | Time (Minutes) | |||
| GEN ET-3100HA | 100kVA | 120 | 12V 18AH | BC01MP-2K | OPT | 5 / 19 | |||
| 60 | 12V 40AH | BC01MP-2K | OPT | 5 / 20 | |||||
| 120 | 12V 24AH | 2 x BC01MP-2K | OPT | 10 / 29 | |||||
| 60 | 12V 70AH | 2 x BC01MP-2K | OPT | 14 / 44 | |||||
| 60 | 12V 80AH | 2 x BC01MP-2K | OPT | 20 / 47 | |||||
| 60 | 12V 105AH | 2 x BC01MP-2K | OPT | 32 / 69 | |||||
| Model | Power | Battery Qty | Battery | Battery Cabinet | Battery Cable Breaker | Time (Minutes) | |||
| GEN ET-3120HA | 120kVA | 120 | 12V 18AH | BC01MP-2K | OPT | 4 / 12 | |||
| 60 | 12V 40AH | BC01MP-2K | OPT | 4 / 14 | |||||
| 120 | 12V 24AH | 2 x BC01MP-2K | OPT | 9 / 23 | |||||
| 60 | 12V 70AH | 2 x BC01MP-2K | OPT | 10 / 34 | |||||
| 60 | 12V 80AH | 2 x BC01MP-2K | OPT | 16 / 39 | |||||
| 60 | 12V 105AH | 2 x BC01MP-2K | OPT | 27 / 58 | |||||
| 120 | 12V 70AH | 4 x BC01MP-2K | OPT | 34 / 84 | |||||
| Model | Power | Battery Qty | Battery | Battery Cabinet | Battery Cable Breaker | Time (Minutes) | |||
| GEN ET-3150HA | 150kVA | 60 | 12V 40AH | BC01MP-2K | OPT | 3 / 9 | |||
| 120 | 12V 24AH | 2 x BC01MP-2K | OPT | 5 / 16 | |||||
| 60 | 12V 70AH | 2 x BC01MP-2K | OPT | 5 / 24 | |||||
| 60 | 12V 80AH | 2 x BC01MP-2K | OPT | 9 / 26 | |||||
| 60 | 12V 105AH | 2 x BC01MP-2K | OPT | 19 / 42 | |||||
| 120 | 12V 70AH | 4 x BC01MP-2K | OPT | 24 / 58 | |||||
| 120 | 12V 80AH | 4 x BC01MP-2K | OPT | 26 / 61 | |||||
| Model | Power | Battery Qty | Battery | Battery Cabinet | Battery Cable Breaker | Time (Minutes) | |||
| GEN ET-3200HA | 200kVA | 60 | 12V 70AH | 2 x BC01MP-2K | OPT | 4 / 14 | |||
| 60 | 12V 80AH | 2 x BC01MP-2K | OPT | 5 / 21 | |||||
| 60 | 12V 105AH | 2 x BC01MP-2K | OPT | 13 / 32 | |||||
| 120 | 12V 70AH | 4 x BC01MP-2K | OPT | 14 / 44 | |||||
| 120 | 12V 80AH | 4 x BC01MP-2K | OPT | 20 / 47 | |||||
| 120 | 12V 105AH | 4 x BC01MP-2K | OPT | 32 / 74 | |||||
| * Battery duration are calculated as %100 and %50 loads. | |||||||||
| * Battery duration are calculated under 0,7 Pf. | |||||||||
| * Generg will supply min. 10 years spare parts for the products. | |||||||||
| * Warranty is 2 years for manufacturer defects. | |||||||||
| Power Factor Options and Suffixes at the end of the model name | |||||||||
| H - PF Cos Ø 0,9 | |||||||||
| HA - PF Cos Ø 0,8 | |||||||||
| HB - Pf Cos Ø 1 | |||||||||