| GROUP PDF | GEN ET-300T SERIES, WITH IGBT RECTIFIER, OUTPUT ISOLATION TRANSFORMER, 10- 400kVA | ||||||
| UPS | BATTERY OPTIONS | TIME | |||||
| Model | Power | Battery Qty | Battery | Battery Cabinet | Battery Cable Breaker | Time (Minutes) | |
| GEN ET-3120T | 120kVA | 104 | 12V 24AH | 2 x BC01MP-2K | OPT | 7 / 19 | |
| 52 | 12V 70AH | 2 x BC01MP-2K | OPT | 9 / 27 | |||
| 52 | 12V 80AH | 2 x BC01MP-2K | OPT | 14 / 31 | |||
| 52 | 12V 105AH | 2 x BC01MP-2K | OPT | 22 / 48 | |||
| 156 | 12V 40AH | 3 x BC01MP-2K | OPT | 27 / 58 | |||
| 104 | 12V 70AH | 4 x BC01MP-2K | OPT | 29 / 66 | |||
| 104 | 12V 80AH | 4 x BC01MP-2K | OPT | 31 / 70 | |||
| 104 | 12V 105AH | 4 x BC01MP-2K | OPT | 48 / 108 | |||
| Model | Power | Battery Qty | Battery | Battery Cabinet | Battery Cable Breaker | Time (Minutes) | |
| GEN ET-3160T | 160kVA | 52 | 12V 70AH | 2 x BC01MP-2K | OPT | 4 / 15 | |
| 52 | 12V 80AH | 2 x BC01MP-2K | OPT | 5 / 22 | |||
| 52 | 12V 105AH | 2 x BC01MP-2K | OPT | 15 / 34 | |||
| 104 | 12V 70AH | 4 x BC01MP-2K | OPT | 18 / 47 | |||
| 104 | 12V 80AH | 4 x BC01MP-2K | OPT | 23 / 50 | |||
| 104 | 12V 105AH | 4 x BC01MP-2K | OPT | 34 / 78 | |||
| 156 | 12V 80AH | 6 x BC01MP-2K | OPT | 37 / 84 | |||
| Model | Power | Battery Qty | Battery | Battery Cabinet | Battery Cable Breaker | Time (Minutes) | |
| GEN ET-3200T | 200kVA | 52 | 12V 80AH | 2 x BC01MP-2K | OPT | 4 / 16 | |
| 52 | 12V 105AH | 2 x BC01MP-2K | OPT | 9 / 27 | |||
| 104 | 12V 70AH | 4 x BC01MP-2K | OPT | 10 / 37 | |||
| 104 | 12V 80AH | 4 x BC01MP-2K | OPT | 17 / 40 | |||
| 104 | 12V 105AH | 4 x BC01MP-2K | OPT | 27 / 59 | |||
| 156 | 12V 80AH | 6 x BC01MP-2K | OPT | 28 / 63 | |||
| 156 | 12V 105AH | 6 x BC01MP-2K | OPT | 43 / 93 | |||
| Model | Power | Battery Qty | Battery | Battery Cabinet | Battery Cable Breaker | Time (Minutes) | |
| GEN ET-3250T | 250kVA | 52 | 12V 105AH | 2 x BC01MP-2K | OPT | 5 / 21 | |
| 104 | 12V 70AH | 4 x BC01MP-2K | OPT | 6 / 26 | |||
| 104 | 12V 80AH | 4 x BC01MP-2K | OPT | 10 / 30 | |||
| 104 | 12V 105AH | 4 x BC01MP-2K | OPT | 20 / 46 | |||
| 156 | 12V 80AH | 6 x BC01MP-2K | OPT | 22 / 50 | |||
| 156 | 12V 105AH | 6 x BC01MP-2K | OPT | 33 / 74 | |||
| Model | Power | Battery Qty | Battery | Battery Cabinet | Battery Cable Breaker | Time (Minutes) | |
| GEN ET-3300T | 300kVA | 104 | 12V 70AH | 4 x BC01MP-2K | OPT | 5 / 19 | |
| 104 | 12V 80AH | 4 x BC01MP-2K | OPT | 6 / 24 | |||
| 104 | 12V 105AH | 4 x BC01MP-2K | OPT | 16 / 38 | |||
| 156 | 12V 70AH | 6 x BC01MP-2K | OPT | 12 / 35 | |||
| 156 | 12V 80AH | 6 x BC01MP-2K | OPT | 17 / 40 | |||
| 156 | 12V 105AH | 6 x BC01MP-2K | OPT | 27 / 59 | |||
| Model | Power | Battery Qty | Battery | Battery Cabinet | Battery Cable Breaker | Time (Minutes) | |
| GEN ET-3400T | 400kVA | 104 | 12V 105AH | 4 x BC01MP-2K | OPT | 9 / 27 | |
| 156 | 12V 70AH | 6 x BC01MP-2K | OPT | 5 / 24 | |||
| 156 | 12V 80AH | 6 x BC01MP-2K | OPT | 10 / 27 | |||
| 156 | 12V 105AH | 6 x BC01MP-2K | OPT | 20 / 43 | |||
| * Battery duration are calculated as %100 and %50 loads. | |||||||
| * Battery duration are calculated under 0,7 Pf. | |||||||
| * Generg will supply min. 10 years spare parts for the products. | |||||||
| * Warranty is 2 years for manufacturer defects. | |||||||